>
Engineering guides

Specify the backup before the rack lands.

Six short guides covering the decisions that shape a BBU project: bridge capacity, ride-through time, parallel architecture, heat, protocols and the certification path. Written for data-center engineers, not for brochures.

Guide index

Six guides, one per design decision

Each guide is short on purpose: the decision, the numbers that drive it, and the traps that show up at commissioning.

DG-01 · Sizing

How to size bridge capacity

Start from measured rack draw, not nameplate. Bridge energy is load in kW times target minutes; compare it against usable capacity per module — 5.12 kWh for VB-5125, 1.5 kWh per node for VB-E3.

  • Count usable capacity, not nameplate
  • Check continuous current: 100 A sustained per VB-5125, 200 A for 10 s peaks
  • Re-check sizing at end-of-life capacity, not new-cell numbers
DG-02 · Ride-through

How to set bridge time

The right target comes from what happens after the bridge: generator start, UPS pickup or a controlled workload migration. VB-E3 anchors the short end — at least 5 minutes at full load, about 20 minutes at quarter load.

  • Under 1 ms transfer covers node ride-through on its own
  • Match minutes to your generator start and escalation plan
  • Migration-window designs are sized from the change plan
DG-03 · Architecture

Parallel banks and current sharing

VB-5125 parallels up to 15 units per bus over CAN. The BMS balances charge and discharge current across the group and isolates any unit that drifts out of bounds.

  • Plan bus current: 100 A continuous per module, times bank size
  • Keep the 15-unit parallel limit in the architecture sketch
  • Verify sharing against your load profile during validation
DG-04 · Thermal

Thermal management and airflow

LFP rewards moderation. VB-5125 charges from 0 to 55 °C and discharges from -20 to 60 °C; VB-E3 lives inside the server loop with cold-plate cooling, specified from -5 to 45 °C.

  • Charging is the tighter window — never below 0 °C without the self-heating variant
  • Map battery telemetry into DCIM from day one
  • Site storage at -40 °C calls for the heated option
DG-05 · Comms

Communication protocol selection

CAN 2.0B runs the bank, RS485 Modbus reaches BMS and EMS layers, SNMP feeds DCIM, and VB-E3 adds PMBus for in-server telemetry. Pick per layer, not per project fashion.

  • SOC estimation at about 0.5% with cell-level voltage and temperature
  • Ask for the protocol register map before commissioning
  • Define alarm routing early — alerts nobody reads are not alerts
DG-06 · Compliance

Certification path planning

Each market wants specific, correctly worded claims: cells UN 38.3 tested, packs designed and tested to IEC 62619, a UL 1973 certification path for North America, CE marked with DoC for the EU.

  • The UN 38.3 Test Summary travels with every shipment
  • UL 9540A test data available per product for bay-level reviews
  • EU battery regulation 2023/1542 is ready-built in; passport rules for over 2 kWh arrive from 2027
Engineering planning desk with rack elevation drawings, load tables and BBU configuration notes
How to use them

Read in order, or jump to your blocker

The guides follow the sequence of a real project: size the load, set the ride-through target, design the bank — then solve heat, communications and compliance before they solve you. Each pairs with a deeper page when you need the detail.

FIG.G3 — Planning desk: guides assume a measured load profile and a target migration window

Quick sizing

From load profile to configuration

A first-pass map from rack draw to a BBU configuration. Indicative only — final sizing is confirmed against your measured load profile.

Load profileBridge targetRecommended configuration
Single AI node, up to 1.5 kW5 min at full load / 20 min at quarter loadVB-E3, one per node
Mixed rack, up to 5 kW30 to 60 min ride-through1 x VB-5125 (5.12 kWh)
Mixed rack, 10 to 15 kW45 to 90 min ride-through4 x VB-5125 (20.5 kWh)
AI rack, 30 to 60 kW (industry-estimated class)Minutes-class bridge to genset6 to 12 x VB-5125 on one bus
±400VDC bay, 80 kW-classRack-level ride-throughVB-H400 bays, paralleled to bay level
Outside these bandsAnything customSend the load profile — we size it with you

FIG.G4 — Indicative configurations; runtime depends on temperature, depth of discharge and cell aging

From guide to build

Your load profile is the only input we need.

Send rack power, bridge target and destination market. We return a sizing note, a configuration and a lead time — usually within 48 hours, always in writing.

Browse spec sheets